Xantrex Technology SW Plus 2524 Power Supply User Manual


 
Advanced Setup
7–8 976-0043-01-02
23 ALM Relays Menu See “23 ALM Relays Menu” on page 7–19 for details.
23A RY9 VDC Energized 44.2 to 71.0 52.0 page 7–20
23B RY9 VDC DeEnergized 40.0 to 71.0 44.0 page 7–20
23C RY9 Delay at DeEngz. Min 00 to 255 10 page 7–20
23D RY10 VDC Energized 20.0 to 64.0 57.6 Vdc page 7–20
23E RY10 VDC DeEnergized 20.0 to 64.0 53.6 Vdc page 7–21
23F RY10 Delay at DeEngz. Min 00 to 255 10 page 7–21
23G RY11 Mode Cooldown Error Error page 7–21
End Menu 23
24 Generator Timers Menu See “24 Generator Timers Menu” on page 7–26 for details.
24A Gen Run Time Start h:m 00:00 to 23:50 08:00 page 7–27
24B Gen Run Time Stop h:m 00:00 to 23:50 08:00 page 7–27
24C Quiet Time Begin h:m 00:00 to 23:50 08:00 page 7–27
24D Quiet Time End h:m 00:00 to 23:50 08:00 page 7–28
24E Gen Exercise Period Days 00 to 255 30 page 7–28
24F Gen Exercise Timer Min 00 to 255 15 page 7–28
24G Gen Cooldown Timer Min 00 to 255 02 page 7–28
24H RN2/Max Gen Run h:m 00:00 to 23:50 08:00 page 7–29
End Menu 24
25 Gen Starting Details Menu See “25 Gen Starting Details Menu” on page 7–29 for details.
25A RY7 Mode GS RN1 RN2 GS page 7–30
25B Gen Warm-up
Second/Minute
0 to 127
/0 to 127
10
Seconds
page 7–37
25C Pre Crank Seconds 00 to 255 10 page 7–37
25D Max Cranking Seconds 01 to 15 10 page 7–37
25E Post Crank Seconds 00 to 255 30
End Menu 25
26 Gen Auto Run Setup Menu See “26 Gen Auto Run Setup Menu” on page 7–38 for details.
Table 7-3
Advanced Setup Default Settings for the Sine Wave Plus Plus 5548 Models
Advanced Setup Menus
Sine Wave Plus 5548
See PageRange/Display
Default
Settings