Xantrex Technology SW Plus 2524 Power Supply User Manual


 
Basic Setup Menu
976-0043-01-02 B–7
12 Battery Charging Menu See “12 Battery Charging Menu” on page 6–19 for details.
12A Finish Stage SILENT
FLOAT
FLOAT SILENT
FLOAT
FLOAT
12B Bulk Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6
12C Float Volts DC 20.0 to 32.0 26.8 40.0 to 64.0 53.6
12D Equalize Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6
12E Max Charge Amps AC 01 to 30 30 01 to 30 30
12F Bulk Done Amps AC 00 to 30 10 00 to 30 10
12G EQ Vdc Done Timer 00:00 to
23:50
02:00 00:00 to
23:50
02:00
12H Max Bulk/EQ Timer 00:00 to
23:50
05:00 00:00 to
23:50
05:00
12I Temp Comp LeadAcid
NiCad
LeadAcid LeadAcid
NiCad
LeadAcid
13 AC Inputs Menu See “13 AC Inputs Menu” on page 6–26 for details.
13A Grid (AC1) Amps AC 00 to 60 60 00 to 60 60
13B Gen (AC2) Amps AC 00 to 60 30 00 to 60 30
13C Input Upper Limit Vac 125 to 150 130 125 to 150 130
13D Input Lower Limit Vac 80 to 115 110 80 to 115 110
14 Save/Restore Settings Menu See “14 Save/Restore Settings Menu” on page 6–29 for details.
14A Push INV now to save
settings
Push INV now to Save Settings
14B Push GEN to restore settings Push GEN to restore settings
14C Push GEN for factory
defaults
Push GEN for factory defaults
Table B-3
Basic Setup Default and User Settings for the Sine Wave Plus 4024 and 4048 Models
Sine Wave Plus 4024 Sine Wave Plus 4048
User
SettingsBasic Setup Menus
Range/
Display Default
Range/
Display Default