Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
Table A. INPUT/OUTPUT Ratings & E xternal W iring Requirements for
Po werw are 9315 Switchboar d Syst em Bypass Mo dule (SSBM):3P3W
(OutputNeutralNotUsed)
Units Rating
Ratings SSBM Model 2500 3000 4000
Maximum Amps 2500 3000 4000
AC
INPUT
(Note 5)
AC Input from UPS to SSBM CBS Breaker
Minimum conductor size, 3∅, (1) neutral, (1) g nd
(number per ∅and neutral)
AWG or
kcmil(ea)
Refer to Table R for minimum
conductor sizes.
AC
INPUT
AC Input to SSBM Bypass
Full Load Current minimum conductor size,
3∅, (1) gnd ( number per ∅)
AWG or
kcmil(ea)
500
(6)
500
(7)
500
(9)
AC
INPUT
(Note 2)
AC Input to optional SMB Bypass
Full Load Current minimum conductor size,
3∅, (1) gnd ( number per ∅)
AWG or
kcmil(ea)
500
(6)
500
(7)
500
(9)
AC
OUTPUT
AC Output from SSBM to Load Bank
Full Load Current minimum conductor size,
3∅, (1) gnd ( number per ∅)
AWG or
kcmil(ea)
500
(6)
500
(7)
500
(9)
AC
OUTPUT
AC Output from SSBM or optional SMB to
Cr it ic al Lo ad
Full Load Current minimum conductor size,
3∅, (1) gnd ( number per ∅)
AWG or
kcmil(ea)
500
(6)
500
(7)
500
(9)
Table B. INPUT/OUTPUT Ratings & E xternal W iring Requirements for
Po werw are 9315 Switchboar d Syst em Bypass Mo dule (SSBM):3P4W
(Output Neutral Used)
Units Rating
Ratings SSBM Model 2500 3000 4000
Maximum Amps 2500 3000 4000
AC
INPUT
(Note 5)
AC Input from UPS to SSBM CBS Breaker
Minimum conductor size,
3∅, (1) neutral, (1) gnd (number per ∅and neutral)
AWG or
kcmil(ea)
Refer to Table R for minimum
conductor sizes.
AC
INPUT
AC Input to SSBM Bypass
Full Load Current minimum conductor size,
3∅, (1) neutral, (1) gnd (number per ∅and neutral)
AWG or
kcmil(ea)
500
(7)
600
(8)
600
(11)
AC
INPUT
(Note 12)
AC Input to optional SMB Bypass
Full Load Current minimum conductor size,
3∅, (1) neutral, (1) gnd (number per ∅and neutral)
AWG or
kcmil(ea)
500
(7)
600
(8)
600
(11)
AC
OUTPUT
AC Output from SSBM to Load Bank
Full Load Current minimum conductor size,
3∅, (1) neutral, (1) gnd (number per ∅and neutral)
AWG or
kcmil(ea)
500
(7)
600
(8)
600
(11)
AC
OUTPUT
AC Output from SSBM or optional SMB to
Cr it ic al Lo ad
Full Load Current minimum conductor size,
3∅, (1) neutral, (1) gnd (number per ∅and neutral)
AWG or
kcmil(ea)
500
(7)
600
(8)
600
(11)