Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
6.2 To install a Supervisory Contact Module:
1. Securely mount t he SCM.
2. Install wiring from the SCM using ½-in. conduit through the cable entry panels
in the top of the S SBM control section (refer to the enclosed switchboard
vendor drawings for the location of the conduit landing plate).
3. If not a lready installed, locate the RMP adapter cable assembly (see
Figure 6---2) in the spare parts k it. Mate the DB---9 connector on the back of
the terminal block to the DB---9 connector (Port 1) on the Customer Interface
Panel of the SSBM (refer to Drawing 164201373---4 in Appendix A). Use tw o
screws from the spare parts kit to secure the terminal block bracket to the
Customer Interface Panel.
TERMINAL
BL OCK
FUSE
(TB3)
Connect to
Po rt 1 (DB --- 9) on
Customer Interface Panel
Figure 6---2. Terminal Block Bracket