AC International SV01B Power Supply User Manual


 
ENGLISH
motor current rating
P1
08 =
SMV output rating
x 1
00
Example: motor = 3 amps; SMV = 4
amps; P108 = 75%
Note
Do not set above the rated motor current as listed on the motor dataplate.
The motor thermal overload function of the SMV is UL approved as a
motor protection device. If line power is cycled, the motor thermal state
is reset to cold state. Cycling power after an overload fault could result in
significantly reducing the motor life.
16
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Minimum
Frequency
0.0 0.0 {Hz} P103 P102, P103 are active for all speed
references
When using an analog speed
reference, also see P160, P161
Maximum
Frequency
60.0 7.5 {Hz} 500
Note
P103 cannot be set below Minimum Frequency (P102)
To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows
(flashing).
- Release s button and wait one second
- Press s button again to continue increasing P1
03
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the
motor/machine may cause damage to equipment and injury to personnel!
Acceleration
Time 1
20.0 0.0 {s} 3600 P104 = time of frequency change
from 0 Hz to P167 (base frequency)
P105 = time of frequency change
from P167 to 0 Hz
For S-ramp accel/decel, adjust P106
Deceleration
Time 1
20.0 0.0 {s} 3600
Example: if P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz;
rate of frequency change from 0 Hz to 120 Hz = 40.0 s
S-Ramp
Integration Time
0.0 0.0 {s} 50.0 P106 = 0.0: Linear accel/decel ramp
P106 > 0.0: Adjusts S-ramp curve
for smoother ramp
(1)
Line Voltage
Selection
1* 0 Low (120, 200, 400, 480VAC) * The default setting is 1 for all
drives except when using “reset
50” (Parameter P199, selection 4)
with 480V models. In this case, the
default setting is 0.
1 High (120, 240, 480, 600VAC)
Motor Overload 100 30 {%} 100
Motor Overload
Type
0 0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
(1) Any changes to this parameter will not take effect until the drive is stopped