Troubleshooting and Diagnostics
Status / Warning Cause Remedy
PID Mode Active Drive has been put into PID
Mode. See P200.
Sleep Mode is active See P240...P242
Start Pending The drive has tripped into a fault
and will automatically restart
(P110 = 3...6)
To disable Auto-Restart, set
P110 = 0...2
PID Mode disabled. Drive has been taken out of PID
Mode. See P200.
Output frequency = 0 Hz
(outputs U, V, W inhibited)
Stop has been commanded from
the keypad, terminal strip, or
network
Apply Start command (Start
Control source depends on
P100)
5.2 Drive Conguration Messages
When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that indicates
how the drive is configured. If the drive is in a Stop state when this is done, the display will also
indicate which control source commanded the drive to Stop
(the two displays will alternate every second).
Conguration Display
Format = x.y.zz x = Control Source:
= Local Keypad
= Terminal Strip
= Remote Keypad
= Network
y = Mode:
= Speed mode
= PID mode
= Vector Torque mode
zz = Reference:
= Keypad s t
= 0-10 VDC (TB-5)
= 4-20 mA (TB-25)
= Jog
= Network
= MOP
= Preset 1...7
Example:
= Local Keypad Start control, Speed mode, Keypad speed reference
= Terminal Strip Start control, PID mode, 0-10 VDC setpoint reference
= Network Start control, Vector Torque mode, Preset Torque #2 reference
Stop Source Display
Format = x
= Stop command came from Local Keypad
= Stop command came from Terminal Strip
= Stop command came from Remote Keypad
= Stop command came from Network