The SMVector drive is designed to operate at the Nominal Output Current (I
n
) shown
in the Ratings tables for most standard applications and industrial environments. The
drive output current or operating temperature may need to be limited as described
below:
For combinations of the above, please consult Lenze / AC Tech applications support
for proper derating.
7
Technical data
480VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
400V 480V 400V 480V 400V 480V
0.5 / 0.37
400 V Three-phase (3/PE)
(
340 … 440 V)
OR
480 V Three-phase (3/PE)
(340 … 528 V)
1.7 1.5 1.3 1.1 175 200 2
3
1 / 0.75 2.9 2.5 2.4 2.
1 175 200 37
1.5 / 1.1 4.2 3
.6 3.5 3.0 175 200 48
2 / 1.5 4.7 4.
1 4.0 3.5 175 200 57
3 / 2.2 6.1 5.4 5.5 4.8 1
75 200 87
5 / 4.0 1
0.6 9.3 9.4 8.2 175 200 128
7.5 / 5.5 1
4.2 12.4 12.6 11.0 175 200 178
10 / 7.5 18.1 15.8 16.1 14.0 175 200 208
600VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
1 / 0.75
600 V Three-phase (3/PE)
(425 …
660 V)
2.0 1
.7 200
37
2 / 1.5 3.2 2.7 200 51
3 / 2.2 4.4 3
.9 200 68
5 / 4.0 6
.8 6.1 200 101
7.5 / 5.5 1
0.2 9 200 148
10 / 7.5 12.4 11 200 1
72
(1) Frequency Range: 48 Hz … 62 Hz
(2) Current Limit (CLim) is a percentage of the output current, I
n
. CLim
max
is the maximum setting for P171.
For 480VAC models, the CLim
max
value in the 480V column of the table is used when P107 is set to 1.
The CLim
max
value in the 400V column is used when P107 is set to 0.
STOP!
Drive Derating
For installations above 1000m a.m.s.l., derate I
n
by 5% per 1000m, do not exceed
4000m a.m.s.l.
Operation above 40°C, derate I
n
by 2.5% per °C, do not exceed 55°C.
• Carrier Frequency (P166):
- If P166=2 (8 kHz), derate I
n
to 92% of drive rating or do not exceed 33°C ambient
- If P166=3 (10 kHz), derate I
n
to 84% of drive rating or do not exceed 27°C ambient