FS-8700-48 Fike Cheetah Manual Page 32 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com
Appendix A.5. Storing Panel Data
Panel data is stored in consecutive locations as described in the map below. For additional
explanations on the meaning of each data element contact FIKE directly.
Array Location
Data Category Data stored at this location
0 Active Counter (0..65535) Active events in normal state
1
Active events in Process state
2 Active events in Trouble state
3 Active events in Supervisory state
4 Active events in Drill state
5 Active events in ? state
6 Active events in ? state
7 Active events in ? state
8 Active events in Abort state
9 Active events in Pre-Alarm1 state
10 Active events in Pre-Alarm2 state
11 Active events in Alarm state
12 Active events in Pre-Discharge state
13 Active events in Release state
14 Active events in Zone Discharge state
15 Active events in Water Mist state
16 Board Status Indicators (0 or 1)
Alarm silence active 1=yes
17 Supervisory Silence Active 1=yes
18 Trouble Silence Active 1=yes
19 AC Power on Main Board 1=ok
20 AC Power on Aux Board 1=ok
21 Walk test Condition 1=on
22 Ground Fault Condition 1=ok
23 Ack Condition 1=on
24 Date & Time Month
25 Day of Month
26 Year
27 Day of Week
28 Hour
29 AM/PM
30 Minute
31 Second
32 Current Event Counter Number of current events present on cheetah
33 LED Status Indicators Pre-Alarm
34 Fire Alarm
35 Supervisory Alarm
36 Trouble
37 AC Power
38 Alarm Silence
39 Supervisory Silence
40 Trouble Silence