Test 1: Input Battery to Input Return—Use the following procedure:
1. Connect one test probe to the A bus BATT input power terminal and the other test probe to
the A bus RTN input power terminal (Figure 7).
Figure 7. Test 1: Input Battery to Input Return
2. Verify that no continuity exists between the BATT input and RTN input terminals.
3. Repeat the test procedure for the B bus.
Test 2: Input Battery to Output Battery—Use the following procedure (Figure 8):
1. Starting on the A bus, at the output terminal for circuit 1, connect the negative test probe to
the bus A input BATT power terminal and the positive test probe to bus A output BATT
power terminal for the circuit being tested.
Figure 8. Test 2: Input Battery to Output Battery
2. Turn on circuit breaker A1.
3. Verify that continuity exists between the specified terminals.
4. Repeat the test procedure for each remaining circuit (A 2-7, B 1-7).
20635-A
TEST 1- POWER BUS A:
VERIFY NO CONTINUITY
EXISTS BETWEEN BATT
AND RTN TERMINALS
TEST 1- POWER BUS B:
VERIFY NO CONTINUITY
EXISTS BETWEEN BATT
AND RTN TERMINALS
20636-A
TEST 2- POWER BUS B:
VERIFY CONTINUITY EXISTS
BETWEEN INPUT AND
OUTPUT BATT TERMINALS
TEST 2- POWER BUS A:
VERIFY CONTINUITY EXISTS
BETWEEN INPUT AND
OUTPUT BATT TERMINALS