2.3 Technical Data
Type power
PROTECT C. 6000 (S) 6000 VA (cos ϕ = 0.7 lag.)
4200 W
PROTECT C.
10000 (S) 10000 VA (cos ϕ = 0.7 lag.)
7000 W
UPS Input (single phase) 1ph
~ / N / PE
Rated connection voltage 220 / 230 / 240 Vac
Voltage tolerance range 176 Vac – 276 Vac ± 3 %
without battery operation
Nominal frequency 50 Hz / 60 Hz
(automatic detection)
Frequency tolerance range ± 4 Hz
Curr. consumption (full load)
PROTECT C. 6000 (S) 31 A
PROTECT C.
10000 (S) 50 A
Input power factor
λ ≥ 0.98
UPS Output (single phase)
Rated output voltage 220 / 230 / 240 Vac ±1 %
(configuration via software
“CompuWatch”)
Nominal frequency 50 Hz / 60 Hz ± 0.1 %
(depending on mains)
Voltage waveform Harmonic distortion
≤ 2% THD (linear load)
≤ 6% THD (non-linear load)
Current Crest Ratio 3:1
Overload behaviour until 105 % continuous;
with existing mains > 105 % - < 130 % for 10 min.;
130 % for 1 s
Gapless automatic switch to SBS.
Cutoff after 1 minute at persisting
overload (backswitch at damping
overload = load < 90%).