AEG 6000 Power Supply User Manual


 
29
5.1 Protection for the personnel
Before setting up the UPS appliance and the external battery
modules (optional accessory) check the following:
Disconnect the unit from the mains.
Protect against reconnection.
Assure for no power.
Ground an short circuit system.
Cover or seals adjacent components still under power.
5.2 Mains connection (general)
To guarantee the correct operation of the UPS and the
optional accessories it is necessary to supply the mains line
with the respective protection.
5.2.1 Checklist for connectors
The connection and grounding terminals are the same for all
the PROTECT C. The cables are connected as follows:
Remove the cover of the terminals.
Introduce the cables from underneath resp. the rear
into the terminals area of the PROTECT C.
Connect the protective conductor terminal (PE) at the
marked position.
Connect the single lines on the respective terminals.
Fix the cable for strain relief to the cable connection
bus-bar.
Check cable for perfect fit, if necessary fasten screw
again.
Remove cable pieces, tools, screws etc. from the
terminal panel.
Fix cover of the terminals again.