Tab. 3 Interpretation of the master setpoint with Thyro-S
Tab. 4 Cyclic input and output data with Thyro-S ..H1
Tab. 5 Cyclic input and output data with Thyro-S ..HRL1
Tab. 5b Thyro-S Faults
Setpoint (Master) Status (return value) (Total setpoint)
0 to 409 = OFF 0 =
410 to 1091 1/5 819
1092 to 1706 = 1/3 1365 =
1707 to 3071 1/2 2047
3072 to 4096 = ON 4096
Offset Input data, actual values Data type Size Unit
0 Load voltage L1 float 4 [V]
4 Mains voltage L1 integer 2 [V]
6 Total setpoint integer 2 4096=100%
8 Fault (see table 5b) integer 2 -
10 Status (see table 5b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Master Setpoint integer 2 4096=100%
Offset Input data, actual values Data type Size Unit
0 Load voltage L1 float 4 [V]
4 Load current L1 float 4 [A]
8 Mains voltage L1 integer 2 [V]
10 Total setpoint integer 2 4096=100%
12 Fault (see table 5b) integer 2 -
14 Status (see table 5b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Master setpoint integer 2 4096=100%
Description Bit LEDs Relay
Frequency measurement outside of 47 Hz to 63 Hz Bit 0 Test LED flashing slowly open
SYNC error, no zero-crossing within the gate Bit 1 Test LED flashing slowly open
Temperature monitoring triggered Bit 2 Load Fault flashing slowly open
Load fault Bit 3 Load Fault on open
Flash values invalid Bit 4 Test LED and Load Fault LED
flashing simultaneously quickly
open
Mains undervoltage (<AD_P_SPG_MIN) Bit 5 Load Fault LED and Test LED on open
Mains overvoltage (>AD_P_SPG_MAX) Bit 6 None closed