American Power Conversion 240-320kW Power Supply User Manual


 
External Connection
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 31
4.4 Relay Board
Relays
All relays are “fail safe”: In alarm modes, relay coil will be de-energized.
Relay shown in alarm position
4.4.1 Relay Board Functions
NOTICE!
If communication to controller lost alarm is active, ALL relays will indicate failure.
Relay Number Message Alarm Trigging Events
1 ##
(X002)
Utility Outside
Tolerance
Utility voltage RMS value outside tolerance
Utility wave form (fast detector) outside tolerance
Utility frequency outside limits
Maximum load: 8.0A – 250VAC
0.3A – 60VDC
Minimum load: 0.05A – 6VAC
0.05A – 6VDC
1
2
3