American Power Conversion 240-320kW Power Supply User Manual


 
46 Installation Guide APC Silcon 240-320kW 480V UPS
990-4049
Programming
5.0 Programming
Below table shows operating parameters programmable from keyboard. Only qualified users
should amend programming parameters.
5.1 Parameters
* Factory settings in bold
** For stystems with avctive Battery Monitor only
*** Do not leave system running in bypass mode (static bypass) for extended periods of time, as
batteries are not recharged in bypass mode.
Parameter Setting* Comments
Bypass operation YES, NO YES will switch the system into bypass
mode***
Language GB, D, F, DK, S, SF,
NL, PL, CZ, E, P, SK,
H
Languages of text in display
Autostart YES, NO Automatic restart by utility return (1 min. delay).
Ensures quick battery recharge.
Remote shutdown active YES, NO Shutdown of UPS by remote signal when in
battery operation. Saves battery energy.
Remote shutdown HIGH, LOW Nature of remote shutdown signal level
Remote shutdown time 0, 1, 2, 3, 4, 5, 6, 7, 8,
9, 10 min.
Time delay on remote shutdown of UPS
Battery capacity test Initiates back-up time check. Time measured
from start until it reaches low DC warning level
(See User Guide, section 6.0).
Battery monitor test ** Initiates checks of battery condition by 25%
discharging.
Automatic battery test** OFF, 3,6 months Activates the battery monitor test in cyclic
intervals.
Battery monitor reset** Press the and key to reset alarm
(flashing light).
Boost charge YES, NO YES results in boost charge (10 hours)
Autoboost charge YES, NO YES results in boost charge after battery
operation (10 hours).
Enter new date YYMMDD Set to local date
Enter new time HHMMSS Set to local time (24 hour clock)