American Power Conversion 240-320kW Power Supply User Manual


 
Installation
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 9
3.0 Installation
3.1 Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from top
or bottom. The system may be installed close to walls as long as free space is allowed for system
doors to open.
For ventilation and service purposes allow for free space of a minimum of 3 foot above and in
front of UPS. Never install systems in direct sunlight.
3.2 Dimensions and Weight
3.2.1 Dimensions and Weight of UPS
WARNING!
For safety reasons do not stand on UPS. Keep UPS cabinet surface free of any objects
UPS
Height
inch/mm
Width
inch/mm
Depth
inch/mm
Weight
lbs./kgs
240kW 480V 70.86/1800 74.80/1900 31.50/800 4432/2014,5
320kW 480V 70.86/1800 74.80/1900 31.50/800 4432/2014,5
Cabinet
74.80/1900 in./mm wide
70.86/1800 in./mm