American Power Conversion AP9215 Power Supply User Manual


 
8
Status
n Status Display 1
Input Line Voltage and Frequency
Output Voltage
Runtime Estimate
Load (in Amps and % of VA capacity)
n Status Display 2
UPS internal temperature
Last Transfer: the cause of the most recent on-battery event.
None - the UPS has not been on battery recently.
Test - a self-test caused the UPS to briefly run on
battery.
Notch/Spike - AC line voltage was non-sinusoidal or se-
verely distorted; includes total power failure.
Low Voltage - AC line voltage went below the lower transfer
point. The lower transfer point is user adjust-
able in certain UPS models, see
Setup:Transfer menu.
Hi Voltage - AC line voltage exceeded the upper transfer
point. The upper transfer point is user adjust-
able in certain UPS models, see
Setup:Transfer menu.
Rate of Chng - abrupt change in line voltage
CirBrkr Trip - input circuit breaker tripped (Symmetra
only)
Status: a terse indication of the state of the UPS. The most
common are On-Line (AC line quality is acceptable), UPS/
Load off, On-battery (load is powered from battery), Low-
Battery (battery is fully discharged), Overload, or any one of
a number of internal faults. Use Diagnostics from the top
level menu for a detail of the UPS status and faults.
Number of installed batteries and bad batteries (Matrix-UPS
and Symmetra only)