American Power Conversion AP9312TH Power Supply User Manual


 
12
Quick Configuration,
continued
Configuring
TCP/IP settings,
continued
Serially through the Control Console. If you are not using a
Windows-based platform, or if you require direct serial
configuration, use a Probe port to configure the
TCP
/
IP
settings
of the Environmental Monitoring Unit’s management card:
1. Connect the supplied configuration cable (
940-0120
) to
an available serial port on your computer and to one of
the Probe ports on the front panel of the unit.
2. Disable PowerChute
plus
,
UNIX
Respond, or any other
service that uses the serial port on the computer.
3. Run a terminal emulator such as Windows
HyperTerminal.
4. Configure the appropriate serial port with the following
settings:
2400
bps, no parity,
8
data bits,
1
stop bit, and
no flow control.
Note: Some terminal emulators such as HyperTerminal
require that you disconnect and reconnect in
order for the new serial settings to take effect.
5. From your computer, press E
NTER
until the user name
prompt appears.
6. Enter the default user name and password (apc for
both).
7. On the Main menu, choose Network.
8. On the Network menu, choose
TCP/IP
.
9. Within the
TCP
/
IP
menu:
a. Disable
BOOTP.
b. Accept changes.
c. Set a valid
IP
address, Subnet Mask and Default
Gateway for your network.
d. Accept changes
e. Press E
SC
until the Main menu appears.
f. From the Main menu, select Logout.
Note: The new settings take effect when you log out.
Continued on next page