4.2.4 4 Circuit Breakers Front Access
To connect the cables to the system proceed as follows:
To connect to the output terminals use M4 ring crimps with cables rated to at least the same
current rating as the corresponding output breaker and colour coded as to meet all the local
installation regulations.
No. of Outputs :
4
Output Rating :
4 O/P’s up to 20A max
2 O/P’s up to 40A max
1 O/P up to 50A max
Circuit Breakers :
Series DC Current trip
Medium time delay
Trip Alarm :
YES
Top Connector = 0V / Earth
(when output earthed)
Bottom Connector :
- 54Vdc, +Ve earth
Distributed Output 4
Output 4
Distributed Output 1
Output 1