American Power Conversion RT XLI/XLICH Power Supply User Manual


 
Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual 25
General
Fault
Need Bat Replacement. One or more battery pairs are in need
of replacement.
Refer to battery installation
procedure.
No Batteries Are
Connected.
No battery power is available. Check that batteries are installed and
connected properly.
Discharged Battery. The UPS is on battery operation and
the battery charge is low.
Shut down the system and the load
or restore the incoming voltage.
Low- Battery. The UPS is on battery operation and
the battery charge is low.
Weak Batt(s) Detected.
Reduced Runtime.
One or more weak battery pairs
detected (only applicable for internal
battery modules).
Replace the weak battery pairs.
Batt Temperature Exceeded
Upper Limit.
The temperature of one or more
battery packs has exceeded system
specifications.
Contact APC Customer Support.
Refer to Contact Information in this
manual.
Battery Over-Voltage
Warning.
The battery voltage is too high and the
charger has been deactivated.
Runtime Is Below Alarm
Threshold.
The predicted runtime is lower than
the user-specified minimum runtime
alarm threshold. Either the battery
capacity has decreased, or the load has
increased.
Option 1) Allow the batteries to
recharge.
Option 2) If possible, increase the
number of battery modules.
Option 3) Reduce the load.
Option 4) Decrease the alarm
threshold.
Condition
PowerView Display
Message
Reason for Message Corrective Action