American Power Conversion RT XLI/XLICH Power Supply User Manual


 
2 Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual
Specifications
Environmental Specifications
Physical Specifications
Temperature
Operating
Storage
32° to 104° F (0° to 40° C)
5
° to 113° F (-15° to 45° C) charge the UPS battery every
six months
86
° to 158° F (30° to 70° C) charge the UPS battery every
three months
This unit is intended for indoor use only.
Select a location sturdy enough to handle
the weight.
Do not operate the UPS where there is
excessive dust or the temperature or
humidity are outside the specified limits.
This unit has front to rear airflow. Allow
adequate space for proper ventilation.
Environmental factors impact battery life.
High temperatures, poor utility power, and
frequent, short duration discharges will
shorten battery life.
Maximum
Elevation
Operating
Storage
10,000 ft (3,000 m)
50,000 ft (15,240 m)
Humidity
0 to 95% relative humidity, non-condensing
Weight (unpacked)
UPS
145 lbs (66 kg)
XL Battery Pack
with eight battery
modules
400 lbs (181 kg)
Each battery
module
38 lbs (17 kg)
Maximum Number of XLBPs Supported by the Smart-UPS XL
10
Dimensions
773 mm
30.4 in
432 mm
17 in
263 mm
10.4 in
102 mm
4 in
482 mm
19 in
465 mm
18.3 in