American Power Conversion 480kW 400V Power Supply User Manual


 
30 Installation Guide APC Silcon 480kW 400V UPS
990-4059
External Connection
4.9.2 APC Battery Breaker Box Connection Diagram (120-480kW)
X009 LED signal from UPS OK to operate corresponding MCCB
X010 MCCB position signals for UPS
X011 Trip for emergency stop (220-240V AC)
4.9.3 UPS with External Battery in Battery Breaker Box/Fuse-box Configuration
UPS Ampere
Rating
[A]
Connection
Cable
[mm2]
Max.
short-
circuit
current [kA]
Dimensions
HxWxD [mm]
Weight
[kg]
480kW 800 3//150 40 1035x835x300 100
Battery 1
Battery 2
Battery 1
Battery 2
UPS
UPS
Main cables are connected directly
to component terminals
?