American Power Conversion 480kW 400V Power Supply User Manual


 
62 Installation Guide APC Silcon 480kW 400V UPS
990-4059
Options/Accessories
NOTICE!
Make sure that gland plate is installed in bottom of cabinet.
CAUTION!
At 100% switch mode load, neutral must be rated for 200% phase current.