American Power Conversion 480kW 400V Power Supply User Manual


 
8 Installation Guide APC Silcon 480kW 400V UPS
990-4059
External Connection
PVC cables insulated to withstand ambient temperature of max. 30°C
** Must be rated as external PE cable if mains system is not supplying PE
4.2 System Integration Interface
UPS External
Input
Fuses* FM
[A]
380-415V
External
Input Cable
[mm2]
380-415V
External PE
Cable
[mm2]
Maximum
External
Output
Fuses*
[A]
External
Output Cable
[mm2]
480kW 1000 3//200 200 800 3//150
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
UPS External Alarm
Cable max.
[mm2]
External System
Earth Cable
[mm2]**
External Battery
Breaker
[A]
External Battery
Cable [mm2]
480kW 2 30 800 3//150
NOTICE!
Install gland plate in bottom of unit.