28 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D
Electrical Specifications
AC Input
WARNING!
Supply the UPS from a dedicated, 3 × 400/230 V, L1, L2, L3, N, PE source or a
high-impedance grounded system.
CAUTION!
Ensure clockwise phase rotation (L1, L2, L3) of input voltages.
CAUTION!
AC and DC disconnect switches and over-current protection must be included in the
installation.
Note
All wiring must comply with all applicable national and/or local electrical codes.
Note
Max. prospective RMS short-circuit current on input terminals: 200 kA
Max. prospective RMS short-circuit current on DC terminals: 50 kA
AC Input
Input rating 800 kW/kVA
Power Factor 1
Input Voltage 380 V
Input Frequency 50 Hz
Nominal input current (note 1) 1132 A
Input Current Limitation (note 2) 1422 A
Input Voltage 400 V
Input Frequency 50 Hz
Nominal input current (note 1) 1203 A
Input Current Limitation (note 2) 1466 A
Input Voltage 415 V
Input Frequency 50 Hz
Nominal input current (note 1) 1159 A
Input Current Limitation (note 2) 1447 A