APC AP8861 Surge Protector User Manual


 
Metered Rack PDU User Guide35
phLowLoad
Access: Administrator, Device User
Description: Set or view the phase low-load threshold in kilowatts. To specify phases, choose from the
following options. Type:
all, a single phase, a range, or a comma-separated list of phases.
Example 1: To set the low-load threshold for all phases to 1 kW, type:
apc> phLowLoad all 1
E000: Success
Example 2: To view the low-load threshold for phases 1 through 3, type:
apc> phLowLoad 1-3
E000: Success
1: 1 A
2: 1 A
3: 1 A
Example 3: To view the low-load threshold for phases 1 on guest Rack PDU 3, type:
apc> phLowLoad 3:1
E000: Success
1: 1 A
phNearOver
Access: Administrator, Device User
Description: Set or view the phase near-overload threshold in kilowatts. To specify phases, choose
from the following options. Type:
all, a single phase, a range, or a comma-separated list of phases.
Example 1: To set the near-overload threshold for all phases to 10 kW, type:
apc> phNearOver all 10
E000: Success
Example 2: To view the near-overload threshold for phases 1 through 3, type:
apc> phNearOver 1-3
E000: Success
1: 10 A
2: 10 A
3: 10 A
phOverLoad
Access: Administrator, Device User
Description: Set or view the phase overload threshold in kilowatts. To specify phases, choose from the
following options. Type:
all, a single phase, a range, or a comma-separated list of phases.
Example 1: To set the overload threshold for all phases to 13 kW, type:
apc> phOverLoad all 13
E000: Success
Example 2: To view the overload threshold for phases 1 through 3, type:
apc> phOverLoad 1-3
E000: Success
1: 13 A
2: 13 A
3: 13 A