APC AP9630 Network Card User Manual


 
9UPS Network Management Card 2 User’s Guide
Local access to the command line interface
For local access, use a computer that connects to the Management Card through the serial port to access
the command line interface:
1. Select a serial port at the computer and disable any service that uses the port.
2. Connect the provided serial cable (APC part number 940-0299) from the selected port on the
computer to the configuration port at the Management Card.
3. Run a terminal program (e.g., HyperTerminal), and configure the selected port for 9600 bps, 8
data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER. At the prompts, enter your user name and password.
Main Screen
Sample main screen
Following is an example of the screen displayed when you log on to the command line interface at the
Management Card.
Information and status fields
Main screen information fields.
Two fields identify the APC operating system (AOS) and application (APP) firmware versions.
The application firmware name identifies the device that connects to the network through this
Management Card. In the example above, the Management Card uses the application firmware for
a Symmetra UPS.
Network Management Card AOS vx.x.x
Symmetra APP vx.x.x
Three fields identify the system name, contact person, and location of the Management Card. (In
the Web interface, select the Administration tab, General in the top menu bar, and
Identification in the left navigation menu to set these values.)
Name : Test Lab
Contact: Don Adams
Location: Building 3
Schneider Electric Network Management Card AOS vx.x.x
(c)Copyright 2009 All Rights Reserved Symmetra APP vx.x.x
--------------------------------------------------------------------------
Name : Test Lab Date : 10/30/2009
Contact : Don Adams Time : 5:58:30
Location : Building 3 User : Administrator
Up Time : 0 Days, 21 Hours, 21 Minutes Stat : P+ N+ A+
APC>