UPS Network Management Card 2 User’s Guide22
Description: Enable IPv6 and view and manually configure these network settings for the Management
Card:
Example 1: To view the network settings of the Management Card, type tcpip6 and press ENTER.
Example 2: To manually configure an IPv6 address of 2001:0:0:0:0:FFD3:0:57ab for the Management
Card, type:
tcpip -i 2001:0:0:0:0:FFD3:0:57ab
uio
Access: Administrator, Device User
Description: This command is available for an AP9631 Network Management Card with a connected
APC Dry Contact I/O Accessory (AP9810).
Example 1: To open the output, type:
uio -rc 2 open
Example 2: To view the status of the devices connected to a Dry Contact I/O Accessory that is installed in
universal input/ output port 2, type:
uio -st 2
Option Argument Description
-S enable | disable Enable or disable IPv6.
-man enable | disable Enable manual adressing for the IPv6 address of the Management Card.
-auto enable | disable Enable the Management Card to automatically configure the IPv6 address.
-i <IPv6 address> Set the IPv6 address of the Management Card.
-g <IPv6 gateway> Set the IPv6 address of the default gateway.
-d6 router | statefull |
stateless | never
Set the DHCPv6 mode, with parameters of router controlled, statefull (for
address and other information, they maintain their status), stateless (for
information other than address, the status is not maintained ), never.
Option Argument Description
-rc <UIO port #> open | close Change the state of a connected output, and specify the UIO
(universal input/ output) port number.
-st
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
View the status of the sensors connected to the Dry Contact
I/O Accessory. To view the status of a specific sensor or
several sensors, type their UIO port numbers.
-disc
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
Identify new input contact or output relay connections.