UPS Network Management Card 2 User’s Guide40
The settings option (including automatic load-shedding)
Click the name of an outlet group to view or configure its settings.
Outlet group name and status. Define the outlet group name or view the state of the outlet.
Sequencing settings. Settings vary by UPS model. Use the sequencing options to define how the UPS
will respond to user-issued commands.
Setting or Field Description
Name A name for the outlet group displayed with the outlet group number wherever the
interface displays that outlet group number.
State Displays the state of the outlet group (on or off).
Setting or Field Description
Power On Delay When this outlet group is off, it waits this delay (up to 600 seconds) before turning on
when Delayed On, Reboot, or Delayed Reboot is selected as the action.
To override Power On Delay, mark the Never checkbox. Only the Immediate On
action will turn on outlets when Never is marked.
Power Off Delay When this outlet group is on, it waits this delay (up to 600 seconds) before turning off
when Delayed Off, Reboot, or Delayed Reboot is selected as the action. (During a
delayed reboot, the outlet group then waits the number of seconds configured as
Reboot Duration and Power On Delay before it turns on.)
To override Power Off Delay, mark the Never checkbox. Only the Immediate Off
action will turn off outlets when Never is marked.
Reboot Duration When this outlet group is on:
•If Reboot is selected as the action, the outlet group turns off immediately and then
waits this delay (up to 600 seconds) before turning on
•If Delayed Reboot is selected as the action, the outlet group waits these three delays:
Power Off Delay before turning off, and Reboot Duration followed by Power On
Delay before turning on.
Min Return Runtime The minimum amount of time the UPS must be able to support the load before it can
turn on again.