APC BC300 Series Power Supply User Manual


 
32 Installation Guide APC BC300 Series 40kW 208/450/480V UPS
990-1401
Clearing the Events Log
5.0 Clearing the Events Log
The events log contains the 250 most recent UPS events, including alarms. To clear the events
log, follow the steps below:
1. Press and at the same time. The display should show Key in password.
2. Using the key pad, enter 920701. The display should show Logging stack is reset. The
events log is now cleared.
3. Press . The display should show Normal operation load power xx%.
If the unit will not be in operation immediately, go to the Start-up and Shutdown Procedure
section.