36 Installation Guide APC BC300 Series 40kW 208/450/480V UPS
990-1401
Technical Specifications
7.2 Battery Specifications
7.3 Dimensions/Weight
40kW
Nominal DC current - Amps 200
UL rating of terminal blocks - AWG
a
a.Terminal block has two positive and two negative
8 mm (=5/16”) studs, hardware provided. Lug re-
quired.
Conductor size may vary based on installation re-
quirements. Size all conductors per applicable
codes.
14 - 2/0
Nominal DC voltage 216
Nominal number of cells 108
Factory-set float charge voltage
b
b.Adjust the float charge voltage setting according
to the battery manufacturer’s recommendations.
246
Charger current limit - Amps
c
c.Programmable to lower level.
20
Inverter efficiency -% 100% load
75% load
50% load
25% load
91
91
89
86
BC300 Series UPS 40kW
Height 59.1 inches
Width 39.4 inches
Depth 31.7 inches