APC BC300 Series Power Supply User Manual


 
Technical Specifications
990-1401
Installation Guide APC BC300 Series 40kW 208/450/480V UPS 35
7.0 Technical Specifications
7.1 APC BC300 Series 40 kW Technical Data
Voltage 3 x 208Y/120 or
208V Delta
450V Delta 3 x 480Y/277
Input Rated input current 146Amps 75 Amps 63Amps
Voltage tolerance
- Utility
- Bypass
+10 / -15
+/- 10
+10 / -15
+/- 10
+10 / -15
+/- 10
Frequency 60Hz
+/- 6%
(standard)
60Hz
+/- 6%
(standard)
60Hz
+/- 6%
(standard)
Current distortion 0-5% THD 0-5% THD 0-5% THD
Bypass tolerance +/- 10% +/- 10% +/- 10%
Output Voltage 3 x 208Y/120 3 x 450Y/277 or
3 x 450 Delta
3 x 480Y/277 or
3x 480 Delta
Voltage tolerance
- Static symmetrical load
- Static asymmetrical load
- Load step
+/- 1
+/- 3
+/- 5
+/- 1
+/- 3
+/- 5
+/- 1
+/- 3
+/- 5
Voltage distortion 0 - 3% (linear
load)
0 - 3% (linear
load)
0 - 3% (linear
load)
Frequency
- Utility synchronized
- Free-running
60Hz
+/- 6%
+/- 0.1%
60Hz
+/- 6%
+/- 0.1%
60Hz
+/- 6%
+/- 0.1%
Overload capacity
- Utility operation 60 seconds
- Utility operation 10 minutes
- Battery operation 60 seconds
- Battery operation 10 minutes
250%
150%
150%
125%
250%
150%
150%
125%
250%
150%
150%
125%
Rated output current 111 Amps 51 Amps 48 Amps
General Temperature
Ambient
Ideal
32 - 104
o
F
77
o
F
32 - 104
o
F
77
o
F
32 - 104
o
F
77
o
F
Humidity (non condensing) Max 95% Max 95% Max 95%
Audible Noise (typical) <65 dBa <65 dBa <65 dBa
Efficiency
AC to AC normal operation
AC to AC economy mode
95%
97%
95%
97%
95%
97%
Heat dissipation - kW (BTU)
Full rated load normal operation
Full rated load economy
mode
0.8 PF load, normal operation
0.8 PF load, economy mode
2.11 (7185)
1.67 (5688)
1.68 (5748)
1.33 (4551)
2.11 (7185)
1.67 (5688)
1.68 (5748)
1.33 (4551
2.11 (7185)
1.67 (5688)
1.68 (5748)
1.33 (4551)