Chapter 3
8 Avaya P333R-LB User’s Guide
Safety
• UL for US approved according to UL195O Std.
• C-UL(UL for Canada) approved according to C22.2 No.950 Std.
• CE for Europe approved according to EN 60950 Std.
• Laser components are Laser Class I approved:
— EN-60825/IEC-825 for Europe
— FDA CFR 1040 for USA
Safety - AC Version
• Overcurrent Protection: A readily accessible Listed safety-approved protective
device with a 16A rating must be incorporated in series with building
installation AC power wiring for the equipment under protection.
Safety - DC Version
• Restricted Access Area: This unit must be installed in Restricted Access Areas
only.
• Installation Codes: This unit must be installed in accordance with the US
National Electrical Code, Article 110 and the Canadian Electrical Code, Section
12.
• Conductor Ampacity: Per UL 1950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply shall have the ampacity of not less than 125
percent of the total connected load. For input leads use at least 18 AWG copper
conductors.
• Overcurrent Protection: Per UL 1950, Annex NAE (NEC Article 240-3), a readily
accessible listed branch-circuit overcurrent protective device rated maximum
10A must be incorporated into the building wiring.
Agency Approvals
EMC Emissions
Approved according to:
• US - FCC Part 15 Subpart B, Class A
• EU - EN55022 Class A
• EU - EN61000-3-2
• Japan - VCCI-A
Immunity
Approved according to:
• EN55024
• EU - EN61000-3-3