18 Cyclades PM IPDU Installer/Administrator/User Guide
To enable current protection status for all units, enter:
To disable current protection status for all units, enter:
NOTE: Current protection commands affect all IPDUs in the daisy chain and all phases of the PM42 IPDU.
currseg
The currseg command lets you view the current for the lower or upper segment of outlets. This
command is only useful for IPDUs with dual current sensors. The lower segment (segment A)
would be outlets 1-5 on a PM10 series IPDU, and the upper segment (segment B) would be outlets
6-10 on a PM10 series IPDU.
Syntax
currseg A|B [reset]
Arguments
Example
To view the current load of segment A, enter:
To reset the maximum recorded current for A and B, enter:
cycle
The cycle command power cycles an outlet or group of outlets. You may use the outlet number or
the outlet name (see command name for details).
Syntax
cycle all|<outlet_string>
pm>currentprotection ON
pm>currentprotection off
A|B
Segment A or segment B
reset
Clear the max recorded current for A and B
pm>currseg A
pm>currseg reset