Bay Technical Associates DS2-RPC Switch User Manual


 
DS-RPC Manual
12
HELP
Typing ‘Help’ at the DS prompt will display a list of commands to change the state of the outlets, unit
configuration, and internal sensor measurements.
Receptacle Controls
On, Off, Reboot, Lock, and Unlock are commands to control the individual outlets.
From the (DS-RPC >) prompt, enter one of the following commands: ON n, OFF n, REBOOT n,
where “n” is the outlet number you want to command.
Example: To turn “On” Outlet 3, type ON 3 from the DS-RPC prompt. The DS responds with:
Type “Y” for yes turns “On” Outlet 3. Observe the status of Outlet 3 has changed to ‘On in the status
menu. Likewise, typing ‘ON ALL’, ‘ON 0’, or ‘ON’ at the DS-RPC > prompt and responding “Y” for
yes, turns ‘On’ all outlets. The OFF n command work similarly as the ON n command.
Enter user name: admin
Average Power: 0 Watts Apparent Power: 26 VA
True RMS Voltage: 124.7 Volts
True RMS Current: 0.1 Amps Maximum Detected: 0.3 Amps
Internal Temperature: 25.0 C
Outlet Circuit Breaker: Good
1)...Outlet 1 : On
2)...Outlet 2 : On
3)...Outlet 3 : On
4)...Outlet 4 : On
Type "Help" for a list of commands
DS-RPC>help
On n <cr> --Turn on an Outlet, n=0,1...4,all
Off n <cr> --Turn off an Outlet, n=0,1...4,all
Reboot n <cr> --Reboot an Outlet, n=0,1...4,all
Status <cr> --DS-RPC Status
Config <cr> --Enter configuration mode
Lock n <cr> --Locks Outlet(s) state, n=0,1...4,all
Unlock n <cr> --Unlock Outlet(s) state, n=0,1...4,all
Current <cr> --Display True RMS Current
Clear <cr> --Reset the maximum detected current
Temp <cr> --Read current temperature
Voltage <cr> --Display True RMS Voltage
Logout <cr> --Logoff
Logoff <cr> --Logoff
Exit <cr> --Logoff
Password <cr> --Changes the current user password
Whoami <cr> --Displays the current user name
Unitid <cr> --Displays the unit ID
Help <cr> --This Command
Turn On Outlet 3 (Y/N)?