24 en | Cable and Wire Standards AutoDome Power Supply Boxes
F.01U.250.895 | 1.0 | 2011.08 Installation Guide Bosch Security Systems, Inc.
3 Cable and Wire Standards
3.1 Power
3.2 Wire Distance Guide
CAUTION!
Installation should only be performed by qualified service
personnel in accordance with the National Electrical Code or
applicable local codes.
CAUTION!
All wires for installation applications must be routed through a
grounded conduit.
24/115/230 VAC
Copper Wire To comply with local codes.
24 V to AutoDome
VA /
Watts
14 AWG (2.5
mm)
16 AWG (1.5
mm)
18 AWG (1.0 mm)
AutoDome 100, Indoor 14 / 7.5 248 m (813 ft) 156 m (512 ft) 98 m (322 ft)
AutoDome 100, Outdoor 47 / 43.5 74 m (242 ft) 46 m (152 ft) 29 m (96 ft)
AutoDome 600, Indoor 27 / 15 129 m (422 ft) 81 m (265 ft) 51 m (167 ft)
AutoDome 600,
Outdoor
1
55 / 51 63 m (207 ft) 40 m (130 ft) 25 m (82 ft)
AutoDome 700, Indoor 35 / 19 99 m (325 ft) 62 m (205 ft) 39 m (129 ft)
AutoDome 700,
Outdoor
2
60 / 55 58 m (190 ft) 36 m (119 ft) 23 m (75 ft)
1. Standard heater module. Add Add 16 W if using VG4-SHTR-XT kit.
2. Standard heater module. The VG4-SHTR-XT kit is not applicable to VG5 700 Series
AutoDomes.