Compaq R6000 Power Supply User Manual


 
Troubleshooting 6-3
Shutdown within 30 seconds Audible Alarm
Table 6-3
Shutdown within 30 seconds Audible Alarm
Audible Alarm Group Audible Alarm Sound Cause(s) Action
Shutdown within 30
seconds
Accelerated beeping.
Begins slowly, and gains
speed as the UPS
approaches shutdown.
UPS shuts down 30 sec
after audible alarm
begins.
Over-temperature. Check the ambient
temperature in the
room. Refer to Appendix
C, “Environmental
Specifications”
If the ambient
temperature is within
range and the over
temperature alarm is
chronic, contact an
authorized service
provider.
Overload. Reduce the load. See
section “Connecting
Loads” in Chapter 2
Low battery. Check the LCD display
(Meters, Battery Volts)
If a shutdown delay has
been programmed, the
accelerated alarm begins
before the last segment
shutoff.
No action needed.
Occurs during the last
minute of sleep timer if
the Sleep mode is
enabled.
No action needed.