Crestron electronic Power Switching Power Supply User Manual


 
CRESTRON GREEN LIGHT™ Power Switching
Appendix B: Module Specifications
Specifications for the GLXP modules are listed in the following table.
GLXP Module Specifications
SPECIFICATION GLXP-SW10 GLXP-SW16 GLXP-HSW8 GLXP-HSW12 GLXP-DIMFLV8
Description
10 Channel
Switch Module
16 Channel
Switch Module
8 Channel High-
Inrush Switch
Module
12 Channel High-
Inrush Switch
Module
8 Channel 0-10V
Fluorescent
Dimmer Module
Number of Outputs
10 16 8 12 8
Cresnet Power
Usage*
5 Watts 5 Watts 5 Watts 5 Watts 5 Watts
Input Voltage 100 – 277 VAC
50/60 Hz
100 – 277 VAC
50/60 Hz
100 – 277 VAC
50/60 Hz
100 – 277 VAC
50/60 Hz
100 – 277 VAC
50/60 Hz
Supported Load
Types
Incandescent,
Magnetic Low
Voltage,
Electronic Low
Voltage,
Neon/Cold
Cathode,
Fluorescent
Ballast, HID,
Motor
Incandescent,
Magnetic Low
Voltage,
Electronic Low
Voltage,
Neon/Cold
Cathode,
Fluorescent
Ballast, HID,
Motor
Incandescent,
Magnetic Low
Voltage,
Electronic Low
Voltage,
Neon/Cold
Cathode,
Fluorescent
Ballast, HID,
Motor
Incandescent,
Magnetic Low
Voltage,
Electronic Low
Voltage,
Neon/Cold
Cathode,
Fluorescent
Ballast, HID,
Motor
Dimmable
Loads:
0-10 VDC
dimmable
fluorescent
ballasts (i.e.
Advance Mark 7
or other ballasts
that comply with
the specifications
for control by DC
voltage in ANSI
C82.11:2002 and
IEC60929:2006)
Non-Dim Loads:
Incandescent,
HID, magnetic low
voltage (MLV),
electronic low
voltage (ELV),
neon/cold
cathode, and
fluorescent
ballasts, motor
Maximum Load
Lighting
Motor
16 A per output
1 HP @ 120V
2 HP @ 230/277V
16 A per output
1 HP @ 120V
2 HP @ 230/277V
16 A per output
½ HP @ 120V
1 HP @ 230V,
1 HP @ 277V
16 A per output
½ HP @ 120V
1 HP @ 230V,
1 HP @ 277V
16 A per output
½ HP @ 120V
1 HP @ 230V,
1 HP @ 277V
Environmental
Temperature
Humidity
Heat Dissipation
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
* Power usage will be zero whenever AC power is present on circuit 1 on the module. Use of Cresnet power is optional.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 15