Eaton Electrical 10640205 Power Supply User Manual


 
Data Power Solutions Quick Start Guide
28
Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.
10640205 February 2009
Specifications
System Input
Input Voltage APU48: L-N: 95-275V RMS
APR48: L-N: 185-275V RMS
Rated Input Current
APS3:
21A (7A per ac power cord)
@ 120V RMS with APU48 rectifiers:
APS6:
42A (7A per ac power cord)
APS3:
10.5A (3.5A per ac power cord)
@ 240V RMS with APU48 rectifiers:
APS6:
21A (3.5A per ac power cord)
APS3:
24A (8A per ac power cord)
@ 208-240V RMS with APR48 rectifiers:
APS6:
48A (8A per ac power cord)
IEC AC Cord Sets
Cable Cable rated according to AC voltage (refer
to the Rated Input Current values) and
local wiring regulations.
Connector 1 (AC supply)
Refer to the Rated Input Current values
according to AC voltage.
Connector 2 (Data Power Solution) IEC type C-13
Frequency Range 45-66Hz
Maximum Earth Leakage Current
1.5mA (per Access Power Rectifier)
System Output
Output Voltage (nominal) 48V
Output Power (maximum)
2.16kW with 3 APU48 rectifiers
APS3-058 and APS3-060:
4.50kW with 3 APR48 rectifiers
1.70kW with 3 APU48 rectifiers
APS3-059 and APS3-061:
3.00kW with 3 APR48 rectifiers
4.32kW with 6 APU48 rectifiers
APS6-058:
9.00kW with 6 APR48 rectifiers
3.40kW with 6 APU48 rectifiers
APS6-059:
7.10kW with 6 APR48 rectifiers
Environment
Ambient Temperature Range (operating)
-10°C to +40°C [+14°F to 104°F]
Relative Humidity (operating and storage)
<95% (non condensing)