Emerson 115-600V Power Supply User Manual


 
Operation
76
Maintenance Mode
For maintenance or repair, the Liebert
®
APM
may be operated in maintenance mode. To place the
Liebert APM in maintenance mode, follow the instructions in 10.4 - Switching the UPS from
Normal Operation to Maintenance Bypass.
Sleep Mode
Sleep mode allows equal run time on all power modules. The modules will put themselves offline for a
programmable period of 0-30 days. Once a module goes offline, another module will come back online.
Each module will rotate being online and offline.
Paralleling Mode
This option is only available on 208V Input Parallel. This mode requires the buyout panel board
paralleling gear. It can parallel the following:
two APM’s
45kW or 90W frames in any module capacity
•redundant
can allow up to 180kVA of load capacity
A Sharing Inductor is required for Parallel units.
!
WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury and death
The UPS input and output must be protected with external overcurrent protection devices. In
maintenance mode, the input and output busbars remain energized and present an electric
shock hazard.
NOTE
To parallel non-208 input voltages, an upstream transformer must drop the input voltage to
208V before the paralleling gear.