Emerson 115-600V Power Supply User Manual


 
Operator Control and Display Panel
87
9.12.3 System Self-Test
When a system self-test is completed, a pop-up window reports the
results of the test, as shown at right.
Press the Help (Enter) key and the pop-up window closes.
9.12.4 Battery Capacity Test Confirmation
When a battery capacity test is started from the Command menu, the
battery will be discharged to low-battery warning level. The Liebert
®
APM
asks for confirmation before the test is started, as shown at
right.
To confirm the choice and begin the battery capacity test, press the Help (Enter) key and the pop-
up window disappears.
To cancel the test, press the F2 (ESC) key. The pop-up window disappears.
9.12.5 Battery Self-Test Aborted, Condition Not Met
When a battery capacity test is started from the Command menu and
the battery self-test condition is inadequate, the Liebert APM will not
perform a battery test. User should check whether the battery state is
boost charging and whether the load level is greater than 20 percent.
Press the Help (Enter) key and the pop-up window closes.
9.12.6 Battery Refresh Charge Aborted, Condition Not Met
When a battery refreshening charge is started from the Command
menu and battery refreshening condition fails to meet requirements,
the Liebert APM will not perform a battery refreshening charge. User
should check if boost charging condition is not enough, such as (No
battery, charger failed, etc.).
Press the Help (Enter) key and the pop-up window closes.
9.12.7 Enter Control Password
When a UPS control operation requires a password, the pop-up at
right will be displayed. The password is 12345.
Use the Right or Left arrow to move the cursor along the password
field. Then use the Up and Down arrows to advance until the desired
number is displayed. Enter the password one digit at a time.
NOTE
For a battery capacity test to function properly, the load must be between 20% and 100%.
System Self-Test finished.
Please check the current
warnings
Battery will be depleted,
Confirm or cancel
Battery Self-Test aborted,
Conditions not met
Battery Refresh Charge
aborted,
Conditions not met
Enter Control Password
*****