Emerson CW Network Card User Manual


 
Blower Duct & Deck Dimensions, CW106 and CW114, Upflow Models
12
6.0 BLOWER DUCT & DECK DIMENSIONS, CW106 AND CW114, UPFLOW MODELS
Model Blower Supply
Motor,
hp
Dimensional Data, inches (mm)
Net Weight
lb. (Kg)AB C DEF
CW106 15 x 15
Top Front 10-15
27-1/2
(699)
3 1/2
(89)
18-11/16
(475)
16-3/16
(411)
10
(254)
4 1/2
(114)
1785
(810)
Top Rear 10-15
27-1/2
(699)
12 5/16
(313)
18 11/16
(475)
16 3/16
(411)
10
(254)
4 1/2
(114)
CW114 15 x 11
Top Front 10-15
30
(762)
3 1/2
(89)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
1925
(873)
20
30
(762)
3 1/2
(89)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
Top Rear 10-20
30
(762)
12 5/16
(313)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
76"
Ref
F
Blower Deck
Front or Rear Air Supply
Top of Unit
DPN001663
Rev. 0
CC CEE
D
35"
Ref
B
Duct Flanges on Three Blowers
122" Ref
A
Front of Unit
Blower Duct Flange Location
2
1
*Follow standard practices on all duct work.
1. Straight section of duct off of unit to be 1.5
to 2.5 times the longest blower dimension.
2. Typical ducting shown, may run to either
side.
TOP-FRONT
SUPPLY SHOWN
1" (25.4mm) Flange
for Decorative
Plenum Alignment
Filter
Access
(both
ends)
Flanges Provided on
Blower Outlets for
Supply Air Ducting
24-1/4" (616mm)
117-1/2"
(2985mm)
2-1/4"
(57mm)
22"
(546mm)
Air
Return
Opening
4"
(102mm)
NOTE: Only 120"
Upflow has rear
return filter box.