7.0 ELECTRICAL SPECIFICATIONS
Table 5 Electrical data—50 Hz systems
Reheat Options Electric None Electric None
Humidifier Options IR/SGH IR/SGH Steam or None Steam or None
Models Motor HP Volts 200 230 380-415 200 230 380-415 200 230 380-415 200 230 380-415
CW026
2.0 FLA 46.7 43.4 24.3 19.8 17.2 9.9 33.9 32.3 17.9 7.0 6.1 3.5
3.0 FLA 49.8 46.1 25.9 22.9 19.9 11.5 37.0 35.0 19.5 10.1 8.8 5.1
CW038
3.0 FLA 62.9 59.0 33.2 22.9 19.9 11.5 50.1 47.9 26.8 10.1 8.8 5.1
5.0 FLA 68.6 63.9 36.0 28.6 24.8 14.3 55.8 52.8 29.6 15.8 13.7 7.9
CW041
3.0 FLA 62.9 59.0 33.2 22.9 19.9 11.5 50.1 47.9 26.8 10.1 8.8 5.1
5.0 FLA 68.6 63.9 36.0 28.6 24.8 14.3 55.8 52.8 29.6 15.8 13.7 7.9
CW051
5.0 FLA 94.6 88.4 49.6 41.2 35.9 20.7 69.2 66.2 36.8 15.8 13.7 7.9
7.5 FLA 103.9 96.5 54.2 50.5 44.0 25.3 78.5 74.3 41.4 25.1 21.8 12.5
CW060
5.0 FLA 107.9 101.4 56.8 41.2 35.9 20.7 82.5 79.2 44.0 15.8 13.7 7.9
7.5 FLA 117.2 109.5 61.4 50.5 44.0 25.3 91.8 87.3 48.6 25.1 21.8 12.5
CW076
7.5 FLA 126.6 122.6 68.6 50.5 44.0 25.3 101.2 100.4 55.8 25.1 21.8 12.5
10.0 FLA 131.7 128.4 71.2 55.6 49.8 27.9 106.3 106.2 58.4 30.2 27.6 15.1
CW084
7.5 FLA 126.6 122.6 68.6 50.5 44.0 25.3 101.2 100.4 55.8 25.1 21.8 12.5
10.0 FLA 131.7 128.4 71.2 55.6 49.8 27.9 106.3 106.2 58.4 30.2 27.6 15.1
CW106
10.0 FLA 131.7 128.4 71.2 55.6 49.8 27.9 106.3 106.2 58.4 30.2 27.6 15.1
15.0 FLA 147.1 142.4 78.9 71.0 63.8 35.6 121.7 120.2 66.1 45.6 41.6 22.8
20.0 FLA 161.5 152.8 86.1 85.4 74.2 42.8 136.1 130.6 73.3 60.0 52.0 30.0
CW114
10.0 FLA 131.7 128.4 71.2 55.6 49.8 27.9 106.3 106.2 58.4 30.2 27.6 15.1
15.0 FLA 147.1 142.4 78.9 71.0 63.8 35.6 121.7 120.2 66.1 45.6 41.6 22.8
20.0 FLA 161.5 152.8 86.1 85.4 74.2 42.8 136.1 130.6 73.3 60.0 52.0 30.0
1. FLA = FULL LOAD AMPS
2. Amperage requirements are based on the rated max FLA current of each component in the unit. The rated max FLA current of the unit is
not the sum total of all components, but is the total of the components which operate during maximum electrical load conditions.
3. The values in the table are for power demand of the unit only.
4. Units are 3-phase, 50-cycle.
5. Consult factory engineering department for electrical requirements of units with variations not listed above.
Table 6 Indoor evaporator fan motor electrical requirements—50Hz systems
Hp Volts 200 230 380-415
2.0 FLA 7.0 6.1 3.5
3.0 FLA 10.1 8.8 5.1
5.0 FLA 15.8 13.7 7.9
7.5 FLA 25.1 21.8 12.5
10.0 FLA 30.2 27.6 15.1
15.0 FLA 46.2 42.0 24.2
20.0 FLA NA NA 30.0
1. Refer to General Data Section for standard fan motor size on units.
2. FLA = Full Load Amps