Electrical Data—Units with EC Fans
5
3.0 ELECTRICAL DATA—UNITS WITH EC FANS
3.1 CW106 and CW114 Electrical Data with EC Fans
3.2 CW181 Electrical Data with EC Fans
Table 1 Electrical data—60Hz-3 phase
Reheat Humidifier Volts FLA WSA OPD
Electric Infrared 460 65.4 81.8 90
Electric Infrared 575 53.4 66.8 70
Electric Infrared 460 53.8 67.3 70
Electric Infrared 575 41.8 52.3 60
None Infrared 460 26.3 32.9 35
None Infrared 575 23.3 29.1 30
None None 460 14.7 15.9 20
None None 575 11.7 12.7 15
Table 2 Electrical data—50Hz-3 phase
Reheat Humidifier Volts FLA WSA
Electric Electric 400 70.8 88.5
Electric None 400 58 72.5
None Electric 400 27.5 34.4
None None 400 14.7 15.9
Table 3 CW181 electrical data—60Hz-3 phase
Reheat Humidifier Volts FLA WSA OPD
Electric Infrared 460 69 86.3 90
Electric Infrared 575 56.4 70.5 80
Electric None 460 57.4 71.8 80
Electric None 575 44.8 56 60
None Infrared 460 29.9 37.4 35
None Infrared 575 26.3 32.9 35
None None 460 18.3 19.8 25
None None 575 14.7 15.9 20
Table 4 CW181 electrical data—50Hz-3 phase
Reheat Humidifier Volts FLA WSA
Electric Electric 400 74.4 93
Electric None 400 61.6 77
None Electric 400 31.1 38.9
None None 400 18.3 19.8