14
Epsilon Eb Digital Servo Drive Installation Manual
Line Fusing and Wire Size
You must incorporate over current protection for the incoming AC power with the minimum
rating shown below. Control Techniques recommends Bussman type: LPN or equivalent.
Epsilon Only
This inrush current specification assumes the drive has been powered off for at least eight
minutes at 40° C ambient or five minutes at 25° C ambient. If this amount of time has not
elapsed since power off, the inrush current will be higher.
Drive Model External AC Line Fuse
Recommended Minimum AC/PE Line
Wire Gauge
Eb-202 LPN 6 Amp 16 AWG
Eb-203 LPN 8 Amp 16 AWG
Eb-205 LPN 12 Amp 16 AWG
Drive Model
Input Voltage
(VAC)
Frequenc
y (Hz)
Input Current
(Amps RMS) at
full drive output
current
Inrush Current (Amps)
1 st Cycle 2nd Cycle
Eb-202
240 / 1 Ø 47 - 63
4.3
140 (2 ms) 20 (2 ms)
Eb-203 6.5
Eb-205 10.8 140 (5 ms) 30 (2 ms)