Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA
Table 2 47-inch cabinet weight
Unit
kVA
Weight, lb (kg)
60 Hz 50 Hz Without Transformer
50 1891 (858) 1966 (892) 1335 (606)
75 1995 (905) 2095 (950) 1335 (606)
100 2191 (994) 2316 (1051) 1335 (606)
125 2298 (1042) 2423 (1099) 1360 (617)
150 2490 (1129) 2640 (1198) 1360 (617)
200 2610 (1184) 2810 (1275) 1360 (617)
225 2800 (1270) 3000 (1361) 1390 (631)
300 2845(1290) 3045 (1381) 1390 (631)
Overall Dim.
39-1/2" (1003mm)
Including hinge
and bezel
projection
Overhead clearance
of 18" (457mm)
recommended
for cooling airflow
Minimum side clearance
of 42" (1067mm) recommended
for service access if unit is
equipped with distribution
monitoring option
Shaded areas indicate
recommended clearance
of 42" (1067mm) at front and
rear for service access
For units with bottom
cable access, clearance
of 6" (152mm) below
unit is recommended
for cooling airflow
and cable entry/exit
Overall Dimension
48.6" (1235mm)
including side panels
78-1/2"
(1995mm)
47"
(1194mm)
36.4"
(925mm)
Unit Base Outline
Cabinet Dimensional Data
Shaded area indicates
cable access and
cooling airflow
Footprint and Floor
Cutout Dimensions
Front
1.3"
(33mm)
1.3"
(33mm)
33.8" (859mm)
35" (889mm)
6" (152mm)
6" (152mm)
Dia. location
3/4" (19mm)
typical
Floor Pedestals
available from
6" (152mm) to
18" (457mm)
9/16" (14mm)
diameter; 4 holes
typical
6" (152mm)
6" (152mm)
Unit Base Outline
Optional Floor Pedestals
36.4" (925mm)
1.5" (38mm)
2.3" (58mm)
Front
47" (1194mm)
43.8"
(1112mm)