Output Voltage Selection
The Output Voltage is user configurable and is designed to allow selecting or
changing the desired output voltage to match the utility via the Liebert
GXT2U Configuration Program provided with the UPS. The settings to choose
from are 200, 208, 220, 230, and 240 VAC output. The factory default setting
is 208 VAC.
!
CAUTION
Never change the voltage settings while the UPS is ON and
powering connected loads.
NOTE
Setting output voltage to 200 VAC will cause the UPS unit to be
derated to 2400 VA, 1680 watts.