Emerson GXT2U Power Supply User Manual


 
29
SPECIFICATIONS
Model Number GXT2-2700RT208
Model Rating 2700VA/1890W
DIMENSIONS: in. (mm)
Unit - W x D x H: in. (mm) 3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping - W x D x H: in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit: lbs (kg) 75.2 (34.1)
Shipping: lbs (kg) 84.9 (38.5)
INPUT AC PARAMETERS
Voltage Range (typical) 208 VAC nominal; variable based on output load
100% - 90% loading 176 VAC/280 VAC
90% - 70% loading 159 VAC/280 VAC
70% - 30% loading 139 VAC/280 VAC
30% - 0% loading 119 VAC/280 VAC
Frequency 40 - 70 Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA L6-20 plug
OUTPUT AC PARAMETERS
Output Receptacles
(2) NEMA L6-15R
(1) NEMA L6-20R
Voltage 200/208/220/230/240 (user configurable) VAC; ±3%
Frequency 50 Hz or 60 Hz
Waveform Sinewave
Main Mode Overload
200% for 8 cycles; 130% for 10 seconds with transfer to
bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty x V x Rating 6 x 12V x 9.0 AH
Battery Mfg/Part #
Panasonic/ UP-VW1245P1
Yuasa/ REW 45-12
Back-Up Time See Battery Run Times charts
Recharge Time
5 Hours to 95% capacity after full discharge into 100% load
(Internal Batteries Only)
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE 587 Category A & B
Transportation ISTA Procedure 1A
DISCONTINUED
PRODUCT