12.0 SPECIFICATIONS
Table 7 UPS specifications—5000, 6000, 8000 and 10,000 models
Model Number GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
Model Rating 4000W/5000VA 4800W/6000VA 7200W/8000VA 9000W/10000VA
Dimensions, Rack Mount, W x D x H
Unit, in. (mm) 16.9 x 26.1 x 6.8 (430 x 662 x 173) 16.9 x 26.5 x 10.3 (430 x 672 x 261)
Shipping, in. (mm) 26.1 x 33.1 x 13.2 (662 x 842 x 336) 24.1 x 32.8 x 16.7 (612 x 832 x 424)
Weight lb (kg)
Unit, lb (kg) 56.2 (25.5) 78.3 (35.5)
Shipping, lb (kg) 70.5 (32) 92.6 (42)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default is 60Hz)
Factory Default VAC 120/208VAC at 120 degrees 120/208VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle 120 degrees 120 degrees
Allowable Input Phase Angle
120, 180, 240 degrees, auto-sensing on application of alternating current
(Restrictions for L-N voltages other than 120VAC)
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120VAC (can be modified with configuration program)
Input Frequency w/o Battery Operation 40 - 70 Hz
Input Power Connection Hardwire Terminal Block 3W + G (L-L-N-G)
L1-N, L2-N Maximum Allowable VAC 150VAC
Output AC Parameters
Factory Default VAC 120/208VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle 120 degrees
Allowable Output Phase Angle 120, 180, 240 degrees, auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC 120VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120VAC, ±2%
L1-N, L2-N, Operating Load Range
105% to 130% 1 Minute
131% to 150% 10 seconds
151% to 200% 1 second
>200% (impact load) At least 5 cycles
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C) 32 to 104 (0 to 40); see Table 9 - Operating temperature parameters
Storage Temp, °F (°C) 5 to 122 (-15 to 50)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A, FCC Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A