Emerson GXT3-6000RT208 Server User Manual


 
Specifications
40
Table 9 Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ±3°C
(pf @ 86°F ±5.4°F)
pf @40°C ±3°C
(pf @ 104°F ±5.4°F)
GXT3-5000/6000RT208 0.8pf 0.8pf
GXT3-6000RTL630 0.7pf 0.7pf
GXT3-8000/10000RT208 0.9pf 0.8pf
Table 10 Internal battery cabinet specifications
Model Number
GXT3-144BATKIT GXT3-240BATKIT
GXT3-288RTBKIT
Used with UPS Model
GXT3-5000RT208
GXT3-6000RT208
GXT3-6000RTL630
GXT3-8000RT208
GXT3-10000RT208
Dimensions, Rack Mount, W x D x H, in (mm)
Unit
8.1 x 19.3 x 2.8
(206 x 490 x 70)
7.2 x 15.4 x 4.4
(184 x 390 x 113)
8.1 x 19.7 x 5.3
(207 x 500 x 135)
Shipping
10.3 x 23.7 x 12.2
(262 x 602 x 310)
10.3 x 18.4 x 7
(262 x 467 x 178)
9.5 x 23.9 x 12.2
(242 x 607 x 310)
Weight lb (kg)
Unit 75.8 (34.4) 45.4 (20.6) 71.1 (32.3)
Shipping 81.1 (36.8) 50.7 (23) 76.4 (34.7)
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating
2 x 6 x 12V x 9.0 AH 20 x 12V x 5.0 AH 2 x 12 x 12V x 9.0 AH
Battery Mfr / Part #
CSB/HR1234W CSB/HR1221W CSB/HR1234W
Backup Time
See Table 14
Recharge Time
3 hours to 90% capacity after full discharge into 100% load
Environmental
Operating Temp, °F (°C) 32 to 104 (0 to 40); see Table 9
Storage Temp, °F (°C) 5 to 122 (-15 to 50)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Agency
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A