Emerson GXT 10KVA Power Supply User Manual


 
Major Components
8
3.0 MAJOR COMPONENTS
The following is a general description of each component and its functions. Please review this section
carefully, as it will give you a better understanding as to how the Nfinity Maintenance Bypass Cabi-
net operates.
3.1 Bypass Switch
The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass
source.
3.2 User Selectable Output Distribution
Several receptacle and hardwire options are available as user selectable output distribution. These
are factory configured when ordered and also allow for field upgrades.
Other Options
Single Position Blanking Plate
Hardwire Option
3.2.1 Optional Transformer
Models offering a transformer are designed to accept the same input voltage as the UPS and provide
240 / 208 / 120 / 120 output. Models with transformers are provided with redundant cooling fans and
user serviceable fan filters. The fans operate only when the system is in Bypass mode.
Table 1 Common receptacle and hardwire options
15 Amp Options 20 Amp Options 30 Amp Options
5-15R2 5-20R2 (T-slot) L5-30R
L5-15R2 L5-20R L6-30R-208
6-15R2-208 L6-20R-208 L6-30R-240
6-15R2-240 L6-20R-240 L14-30R-240
L6-15R2-208 L14-20R-240
30A,120V, 1 pole breaker w/ 1/2" &
3/4" knockouts
L6-15R2-240
20A,120V, 1 pole breaker w/ 1/2" &
3/4" knockouts
30A,208V, 2 pole breaker w/ 1/2" &
3/4" knockouts
15A,120V, 1 pole breaker w/ 1/2" &
3/4" knockouts
20A,208V, 2 pole breaker w/ 1/2" &
3/4" knockouts
30A,240V, 2 pole breaker w/ 1/2" &
3/4" knockouts
15A,208V, 2 pole breaker w/ 1/2" &
3/4" knockouts
20A,240V, 2 pole breaker w/ 1/2" &
3/4" knockouts
15A,240V, 2 pole breaker w/ 1/2" &
3/4" knockouts